Cameras, Racks and Power · #82
Online UPS Load and Runtime Calculator
Estimates whether the UPS carries the load and how many minutes the battery lasts.
- Data is processed in your browser and not sent to a server
Tool
What does this tool do?
UPSs are sold by VA but the limit is usually the W rating (VA × power factor). Above 80 % load both life and runtime drop quickly. The tool checks load percentage by W and VA; with battery voltage and capacity it gives an approximate runtime from energy.
How to use it
- Enter the UPS VA rating and power factor, or the W rating directly.
- Enter the connected load (measured W).
- Enter battery bus voltage, Ah and number of strings, optionally efficiency and depth of discharge; enter the target time and press Run.
Fields
- UPS rating (VA)
- UPS power factor
- W = VA × PF; from datasheet.
- UPS rating (W)
- Instead of VA if known.
- Connected load
- Measured or calculated W.
- Load power factor
- 0.9–0.99 for modern PSUs.
- Battery bus voltage
- E.g. 6 × 12 V in series = 72 V.
- Battery capacity
- Ah of one battery.
- Parallel strings
- Extra battery modules.
- Inverter efficiency
- Usable discharge
- 80 % typical for lead-acid.
- Required time (min)
- Generator start or shutdown time.
Worked example
| Input | Value |
|---|---|
| UPS rating (VA) | 3000 |
| UPS power factor | 0.9 |
| Connected load | 1200 |
| Load power factor | 0.9 |
| Battery bus voltage | 72 |
| Battery capacity | 9 |
| Parallel strings | 1 |
| Inverter efficiency | 90 |
| Usable discharge | 80 |
| Required time (min) | 15 |
Expected result: A 3000 VA / 2700 W UPS at 1200 W load is 44 %; a 72 V 9 Ah battery holds 648 Wh, about 23 min; the 15-minute target is met.
Real runtime may be shorter due to battery age, temperature and capacity loss at high current (Peukert effect); use the vendor's runtime chart for new batteries and a real outage test for older ones.
Second scenario
| Input | Value |
|---|---|
| UPS rating (VA) | 1500 |
| UPS power factor | 0.9 |
| Connected load | 1250 |
| Load power factor | 0.9 |
| Battery bus voltage | 24 |
| Battery capacity | 9 |
| Parallel strings | 1 |
| Inverter efficiency | 90 |
| Usable discharge | 80 |
| Required time (min) | 10 |
Expected result: A 1500 VA UPS at 1250 W is 93 % (amber); with a 24 V 9 Ah battery ~7.5 min, below the 10-minute target.
Method and assumptions
Rated W = VA × PF (or the W entered). Load % = load / rated W. VA use = load / load PF. Energy (Wh) = bus voltage × Ah × strings. Runtime (h) = Wh × efficiency × depth of discharge / load.
Using the result and troubleshooting
Keep load below 80 %; if runtime is short, plan extra battery modules or a bigger UPS. Take the total load from the Power and Cooling tool or the PDU calculation.
Limits and common mistakes
- Peukert effect, temperature, battery ageing and the UPS's own consumption are not in the linear model; the result does not replace vendor curves.
Frequently asked questions
What is the difference between VA and W?
VA is apparent power, W is real (active) power. A UPS has two limits such as 3000 VA and 2700 W; the load must exceed neither.
Related tools and service
- PDU A/B Load CalculatorShows in an A/B-fed rack whether the remaining feed carries the load when one feed is lost.
- Server Power and Cooling CalculatorCalculates energy, heat load and cost from device power consumption.
Related service: UPS and Power Continuity for Camera Systems