Cameras, Racks and Power · #83
Online PDU A/B Load Calculator
Shows in an A/B-fed rack whether the remaining feed carries the load when one feed is lost.
- Data is processed in your browser and not sent to a server
Tool
What does this tool do?
Dual-PSU servers normally share load equally between two PDUs, but when one feed drops the whole load moves to the other. If both PDUs are above 50 % in normal operation, the breaker trips at the first failure and redundancy is useless. The tool compares normal and failure scenarios with the limit.
How to use it
- Enter devices as
name;W;PSU count;feed;qty. With 1 PSU feed is A or B; empty means alternate. - Enter voltage, PDU/breaker current, phase and continuous load limit (80 %).
- Press Run.
Fields
- Devices
- name;W;PSU (1/2);feed (A/B);qty — W is measured average.
- Voltage
- Phase-neutral for single phase, phase-phase for three phase.
- PDU / breaker current
- Phase
- Continuous load limit
- North American rule 80 %; apply local regulations.
Worked example
| Input | Value |
|---|---|
| Devices | |
| Voltage | 230 |
| PDU / breaker current | 16 |
| Phase | Single phase |
| Continuous load limit | 80 |
Expected result: Normally A 1,470 W, B 1,370 W; if A fails B carries 2,720 W, if B fails A carries 2,820 W. Limit 2,944 W (16 A × 230 V × 80 %): sufficient but tight at 96 %.
The single-PSU NVR is on A only; recording stops if A fails. If critical, feed the NVR through an automatic transfer switch (ATS). Plan a second PDU pair before adding devices.
Second scenario
| Input | Value |
|---|---|
| Devices | |
| Voltage | 400 |
| PDU / breaker current | 16 |
| Phase | Three phase |
| Continuous load limit | 80 |
Expected result: 3 blade chassis, 400 V 16 A three phase: normally 4,500 W per feed, 9,000 W on failure; exceeds the 8,868 W limit.
Method and assumptions
Dual PSU: load split equally in normal operation, all on the remaining feed on failure. Single PSU: full load on its feed; the device shuts down if that feed fails. Capacity = V × A (× √3 for three phase); limit = capacity × continuous load share.
Using the result and troubleshooting
Keep each feed's normal load below 50 % of the limit. Take watts from iDRAC/iLO or smart PDU readings; nameplate values mislead.
Limits and common mistakes
- Phase imbalance and sub-breaker banks on the PDU (e.g. 2 × 8 A) are not modelled; dual PSUs may share unequally.
Frequently asked questions
How many watts does a 16 A outlet carry?
3,680 W in theory at 230 V; 2,944 W is planned for continuous load at 80 %.
Related tools and service
- UPS Load and Runtime CalculatorEstimates whether the UPS carries the load and how many minutes the battery lasts.
- Rack Unit Layout PlannerPlaces devices at U positions and shows overlaps and devices that do not fit.
Related service: UPS and Power Continuity for Camera Systems