Cameras, Racks and Power · #83

Online PDU A/B Load Calculator

Shows in an A/B-fed rack whether the remaining feed carries the load when one feed is lost.

  • Data is processed in your browser and not sent to a server

Tool

name;W;PSU (1/2);feed (A/B);qty — W is measured average.

Phase-neutral for single phase, phase-phase for three phase.

North American rule 80 %; apply local regulations.

What does this tool do?

Dual-PSU servers normally share load equally between two PDUs, but when one feed drops the whole load moves to the other. If both PDUs are above 50 % in normal operation, the breaker trips at the first failure and redundancy is useless. The tool compares normal and failure scenarios with the limit.

How to use it

  1. Enter devices as name;W;PSU count;feed;qty. With 1 PSU feed is A or B; empty means alternate.
  2. Enter voltage, PDU/breaker current, phase and continuous load limit (80 %).
  3. Press Run.

Fields

Devices
name;W;PSU (1/2);feed (A/B);qty — W is measured average.
Voltage
Phase-neutral for single phase, phase-phase for three phase.
PDU / breaker current
Phase
Continuous load limit
North American rule 80 %; apply local regulations.

Worked example

InputValue
Devices
Sunucu;450;2;;4
Storage;600;2
Switch;150;2;;2
NVR;120;1;A
Modem;20;1;B
Voltage230
PDU / breaker current16
PhaseSingle phase
Continuous load limit80

Expected result: Normally A 1,470 W, B 1,370 W; if A fails B carries 2,720 W, if B fails A carries 2,820 W. Limit 2,944 W (16 A × 230 V × 80 %): sufficient but tight at 96 %.

The single-PSU NVR is on A only; recording stops if A fails. If critical, feed the NVR through an automatic transfer switch (ATS). Plan a second PDU pair before adding devices.

Second scenario

InputValue
Devices
Blade şasi;3000;2;;3
Voltage400
PDU / breaker current16
PhaseThree phase
Continuous load limit80

Expected result: 3 blade chassis, 400 V 16 A three phase: normally 4,500 W per feed, 9,000 W on failure; exceeds the 8,868 W limit.

Method and assumptions

Dual PSU: load split equally in normal operation, all on the remaining feed on failure. Single PSU: full load on its feed; the device shuts down if that feed fails. Capacity = V × A (× √3 for three phase); limit = capacity × continuous load share.

Using the result and troubleshooting

Keep each feed's normal load below 50 % of the limit. Take watts from iDRAC/iLO or smart PDU readings; nameplate values mislead.

Limits and common mistakes

  • Phase imbalance and sub-breaker banks on the PDU (e.g. 2 × 8 A) are not modelled; dual PSUs may share unequally.

Frequently asked questions

How many watts does a 16 A outlet carry?

3,680 W in theory at 230 V; 2,944 W is planned for continuous load at 80 %.

Related tools and service

Related service: UPS and Power Continuity for Camera Systems