Cameras, Racks and Power · #82

Online UPS Load and Runtime Calculator

Estimates whether the UPS carries the load and how many minutes the battery lasts.

  • Data is processed in your browser and not sent to a server

Tool

W = VA × PF; from datasheet.

Instead of VA if known.

Measured or calculated W.

0.9–0.99 for modern PSUs.

E.g. 6 × 12 V in series = 72 V.

Ah of one battery.

Extra battery modules.

80 % typical for lead-acid.

Generator start or shutdown time.

What does this tool do?

UPSs are sold by VA but the limit is usually the W rating (VA × power factor). Above 80 % load both life and runtime drop quickly. The tool checks load percentage by W and VA; with battery voltage and capacity it gives an approximate runtime from energy.

How to use it

  1. Enter the UPS VA rating and power factor, or the W rating directly.
  2. Enter the connected load (measured W).
  3. Enter battery bus voltage, Ah and number of strings, optionally efficiency and depth of discharge; enter the target time and press Run.

Fields

UPS rating (VA)
UPS power factor
W = VA × PF; from datasheet.
UPS rating (W)
Instead of VA if known.
Connected load
Measured or calculated W.
Load power factor
0.9–0.99 for modern PSUs.
Battery bus voltage
E.g. 6 × 12 V in series = 72 V.
Battery capacity
Ah of one battery.
Parallel strings
Extra battery modules.
Inverter efficiency
Usable discharge
80 % typical for lead-acid.
Required time (min)
Generator start or shutdown time.

Worked example

InputValue
UPS rating (VA)3000
UPS power factor0.9
Connected load1200
Load power factor0.9
Battery bus voltage72
Battery capacity9
Parallel strings1
Inverter efficiency90
Usable discharge80
Required time (min)15

Expected result: A 3000 VA / 2700 W UPS at 1200 W load is 44 %; a 72 V 9 Ah battery holds 648 Wh, about 23 min; the 15-minute target is met.

Real runtime may be shorter due to battery age, temperature and capacity loss at high current (Peukert effect); use the vendor's runtime chart for new batteries and a real outage test for older ones.

Second scenario

InputValue
UPS rating (VA)1500
UPS power factor0.9
Connected load1250
Load power factor0.9
Battery bus voltage24
Battery capacity9
Parallel strings1
Inverter efficiency90
Usable discharge80
Required time (min)10

Expected result: A 1500 VA UPS at 1250 W is 93 % (amber); with a 24 V 9 Ah battery ~7.5 min, below the 10-minute target.

Method and assumptions

Rated W = VA × PF (or the W entered). Load % = load / rated W. VA use = load / load PF. Energy (Wh) = bus voltage × Ah × strings. Runtime (h) = Wh × efficiency × depth of discharge / load.

Using the result and troubleshooting

Keep load below 80 %; if runtime is short, plan extra battery modules or a bigger UPS. Take the total load from the Power and Cooling tool or the PDU calculation.

Limits and common mistakes

  • Peukert effect, temperature, battery ageing and the UPS's own consumption are not in the linear model; the result does not replace vendor curves.

Frequently asked questions

What is the difference between VA and W?

VA is apparent power, W is real (active) power. A UPS has two limits such as 3000 VA and 2700 W; the load must exceed neither.

Related tools and service

Related service: UPS and Power Continuity for Camera Systems

CCTV online tools · See all online tools